Stöbich ECClos Flex

Product Description

Vertically closing fire protection closure for wall openings in the course of track-bound conveyor systems with unsplit or split conveyor technology in the closing area.

World novelty:
The world‘s first conveyor system closure of textile construction with European Technical Assessment (ETA)

Type

Fire protection closure in the course of railway-bound conveyor systems

Verification

ETA-21/0359 | VKF approval no. 32476

Closing direction

from top to bottom

Fire resistance

EI2 90 | tested according to DIN EN 1366-7:2004-09 | classified according to EN 13501-2:2007

Closing cycles

C | tested according to EN 12605:2000-08 | classified according to EN13501-2:2016 For scheduled open closures

Reopening

motor

Visible surfaces

Cover, guide rails and winding housing
Stainless steel 1.4301 (V2A)
coated in RAL color

Fest panel
untreated fire protection panels
painted with emulsion paint in a similar RAL color
Sheet metal cladding stainless steel 1.4301 (V2A)
Sheet metal cladding coated in RAL color

Size dimensions and system design
Due to the combination of classifications or the ratio of clear system width to clear system height, the stated maximum dimensions may be reduced and the dimensions of the enclosure and guide rails may vary. The specifications on the quotation apply.

Component (supporting structure) in which the closure may be installed

Achievable fire resistance class

clear wall opening

Component (supporting structure) in which the closure may be installed

Achievable fire resistance class

clear wall opening

clear wall opening width

clear wall opening

clear wall opening height

Component (supporting structure) in which the closure may be installed

High-density solid wall, masonry or solid concrete with total density of ≥ 800 kg/m3 and a thickness of ≥ 150 mm

Achievable fire resistance class

EI2 90

clear wall opening

from 500 mm to 6,000 mm

clear wall opening

from 500 mm to 4,400 mm

Component (supporting structure) in which the closure may be installed

Low density solid wall, aerated concrete with total density of ≥ 450 kg/m3 and a thickness of ≥ 150 mm

Achievable fire resistance class

EI2 90

clear wall opening

from 500 mm to 6,000 mm

clear wall opening

from 500 mm to 4,400 mm

The installation situation must comply with the building code requirements of the country of installation. The fire resistance of a ceiling or wall support structure and the adjacent components must at least cor- respond to that of the fire protection closure. Proof of the stability and serviceability of the adjacent walls and components must be provided under general ambient conditions and in the event of fire. See also notes on the standard supporting structure in EN1366-7:2004 or EN1363-1:2020. The fire protection system must not be subjected to any additional loads other than its own weight, even in the event of fire.

Dimensions at the end of the conveyor system Closing direction vertical from top to bottom

A - Clear wall opening width

500 mm to 6000 mm

B - Clear wall opening height

500 mm to 4400 mm

C - Lower edge of wall opening

0 - n

I - Planning allowance left

Default value 20 mm

J - Planning allowance right

Default value 20 mm

K - Planning surcharge above

Default value 20 mm

L - Planning surcharge below

Wall-hung system: default value = 20 mm
Floor-standing system: default value = 0 mm

Q - Conveyor separation Width

Depending on the position and type of the conveyor system and the size of the clear wall opening dimensions

R - Conveyor separation dimension wall side

Depending on the position and type of the conveyor system and the size of the clear wall opening dimensions

S - Conveyor separation dimension room side

Depending on the position and type of the conveyor system and the size of the clear wall opening dimensions

N - Clearance height/headroom

Depending on the position and type of the conveyor system and the size of the clear wall opening dimensions

M - support level

0 - n

W - conveying level protrusion

up to +25 mm

AA - Space requirement above the opening

BF + BW + K
unseparated continuous conveying = 200 mm + 430 mm + 20 mm = 650 mm
separated conveyor technique = 50 mm + 430 mm + 20 mm = 500 mm

AB - Space requirement below the opening

with fixed panel = L + AS + AO = 20 mm + 80 mm + 120 mm = 220 mm
without fixed field = 0 mm

AG - Space requirement drive Installation side

800 mm

AH - Sealing depth at the shut-off element

150 mm

AI - Sealing depth at the fixed panel

175 mm

AJ - Thickness barrier element

approx. 12 mm

AK - Total fixed field width

AL + AM + AN

AL - Fixed field width

A + I + J + CD + CD = A + 20 mm + 20 mm + 230 mm + 230 mm = A + 500 mm

AM - Fixing projection fixed panel left

50 mm

AN - Fixing projection fixed panel right

50 mm

AO - Fixing protrusion fixed panel below

120 mm

AQ - Space requirement for wall frame to the left of the opening

I + BD + CD + 100 mm = 20 mm + 50 mm + 230 mm + 100 mm = 400 mm

AR - Traverse path of shut-off element / unwinding length

= N

AS - Overlap fixed field below

80 mm

AT - Overlap fixed field left

215 mm

AU - Overlap fixed field right

215 mm

AV - Space requirement wall frame to the right of the opening

J + BE + CD + 100 mm = 20 mm + 50 mm + 230 mm + 100 mm = 400 mm

AW - Fixed field depth

175 mm

AX - Height wall frame

N + AA
unseparated continuous conveyor = N + 650 mm
separated conveyor technique = N + 500 mm

AY - System height

BI + AX

BB - Drive Technology Width

750 mm

BC - Drive Technology Height

430 mm

BD - Offset left

50 mm

BE - Offset right

50 mm

BF - Offset top

unseparated continuous conveyor = 200 mm
separated conveyor technology = 50 mm

BH - fixed field height

M - C + L + AS

BI - Total fixed field height

BH + AO

BJ - System width

AQ + AV + A = 400 mm + 400 mm + A

BV - Winding case width

= BJ

BW - Winding case height

430 mm

BX - Winding case depth

460 mm

BY - Drive housing width

750 mm

BZ - Drive housing height

430 mm

CA - Drive housing depth

340 mm

CB - Parking area Shut-off element under winding housing

unseparated continuous conveyor = 200 mm
separated conveyor technology = 0 mm

CC - Thickness barrier element on reopening

400 mm

CD - Guide rail width

230 mm

CE -Guide rail depth

114 mm

CF - Guide rail height

AX - BW

CG - Separation point conveyor system guide width

300 mm

CH - Separation point conveyor guide dimension wall side

0 mm

CI - Separation point conveyor guide dimension room side

300 mm

CJ - width/height ratio

”BJ/CF

Make an Inquiry

Protect your building with intelligent fire and smoke protection solutions engineered for performance, reliability, and architectural flexibility. Whether you’re planning a new project, upgrading an existing facility, or exploring specialized safety systems, Stöbich delivers advanced protection tailored to your exact requirements. Make an inquiry today and discover how our innovative fire protection technologies can help safeguard people, property, and operations with confidence.

Name(Required)
Email(Required)

About Our ECClos-Flex

ECClos-Flex is Stöbich’s innovative textile-based conveyor system closure designed for wall openings used by track-bound conveyor systems. As the first textile conveyor closure to receive a European Technical Assessment (ETA), the system combines certified fire protection, operational flexibility, and seamless integration into modern automated material handling environments.

The First Textile Conveyor Closure with ETA Certification

ECClos-Flex represents a significant advancement in conveyor fire protection technology as the world’s first textile-based conveyor system closure to achieve a European Technical Assessment (ETA).

This certification demonstrates compliance with demanding European performance and safety standards while providing building owners, engineers, and facility managers with confidence in the system’s fire protection capabilities.

    Protecting Conveyor Openings in Fire-Rated Walls

    Modern manufacturing facilities, warehouses, and logistics centers depend on conveyor systems that frequently pass through fire-resistant walls and partitions.

    These openings can become pathways for flames, smoke, and heat during a fire event if left unprotected. ECClos-Flex automatically seals conveyor penetrations during emergencies, restoring the integrity of the fire-rated barrier and helping maintain effective fire compartmentation throughout the facility.

    Designed for Modern Conveyor Systems

    One of the key advantages of ECClos-Flex is its ability to accommodate both split and unsplit conveyor technologies within the closing area.

    This flexibility makes the system suitable for a wide range of applications, including:

    • Manufacturing facilities
    • Warehouses
    • Distribution centers
    • Logistics hubs
    • Automated production environments

    By integrating directly into existing conveyor infrastructure, ECClos-Flex supports uninterrupted material flow during normal operations while ensuring dependable fire protection when needed.

    Innovative Textile-Based Construction

    Unlike traditional rigid conveyor closures, ECClos-Flex utilizes an advanced textile-based design.

    Benefits of the textile construction include:

    • Greater design flexibility
    • Reduced structural complexity
    • Adaptable installation options
    • Improved accommodation of complex conveyor layouts
    • Efficient integration into automated systems

    This innovative approach allows facilities to implement effective fire protection without the limitations often associated with conventional closure systems.

    Automatic Vertical Fire Closure

    ECClos-Flex features a vertically closing design engineered for rapid deployment during emergency situations.

    When activated by a fire alarm or detection system, the closure automatically deploys to seal the wall opening and prevent the spread of fire, smoke, and heat between compartments.

    This fast, automatic response helps preserve compartmentation and supports safer conditions throughout the facility.

    Built for Demanding Industrial Environments

    Industrial conveyor systems often operate continuously in challenging conditions that include:

    • Heavy usage
    • Continuous material movement
    • Dust exposure
    • Vibration
    • Around-the-clock operation

    ECClos-Flex is engineered for long-term reliability within these demanding environments while minimizing disruption to day-to-day operations.

    Supporting Flexible Facility Design

    The textile-based construction of ECClos-Flex provides engineers and designers with greater freedom when planning conveyor layouts and compartmentation strategies.

    By reducing the bulk and structural limitations commonly associated with traditional fire closures, the system supports more efficient integration into modern industrial and logistics facilities.

    Advanced Fire Protection for Automated Facilities

    ECClos-Flex combines:

    • ETA-certified performance
    • Textile-based innovation
    • Automatic fire closure deployment
    • Conveyor system compatibility
    • Long-term industrial reliability

    The result is an intelligent fire protection solution that helps facilities maintain automation efficiency while providing critical protection against the spread of fire and smoke.