Stöbich Fire and Smoke Curtain HC

Product Description

In the event of an alarm, a room-enclosing or radiation-reducing textile fire protection closure that closes by means of an electric motor in a horizontal installation position and closing direction.

Type

Radiation-reducing, room-enclosing fire protection closure of textile design

Verification

CE marking according to hEN 16034 : 2014 in conjunction with hEN 13241 : 2003+A2 : 2016

Closing direction

horizontal

Fire resistance

E 120 | EW 90 | tested according to EN 1634-1 : 2014-03 | classified according to EN 13501-2 : 2016-12

Closing cycles

C, C1 | tested according to EN 12605 : 2000-08 | classified according to EN 13501-2 : 2016-12

Durability

C: for 2-part systems up to size 9400 x 18800 mm for E 120 and EW 60 or 6800 x 4270 mm for EW 90
C1: for 1-part systems up to size 5000 x 5000 mm for EW 60 or 6000 x 6500 mm for E 120 and EW 30

Environmental conditions

In the event of a fire, the falling of ceiling parts in the area of the the area of the soffit by suitable on-site measures on the part of the customer. Not taken into account are special environmental conditions (for example Humidity >80%, ambient | Special environmental conditions are not taken into account (e.g. humidity > 80 %, ambient temperature < 5 °C and > 45 °C, wind loads etc.)

Legend System components:
1 = Smoke detector
2 = Housing
3 = Guide rails
4 = Textile
5 = End element
6 = Tubular motor
7 = Control module
8 = Control with operating unit
9 = Manual release

Structural system design (system drawing)

Classification

Size** [y x r] in mm

Type

Fabric

Wall Thickness* in mm

Housing (t x h) in mm

Guide Rail in mm

Classification

E 120

Size** [y x r] in mm

6000 x 6500

Type

1-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

235 x 320

Guide Rail in mm

200 x 80

Classification

EW 30

Size** [y x r] in mm

6000 x 6500

Type

1-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

235 x 320

Guide Rail in mm

200 x 80

Classification

EW 60

Size** [y x r] in mm

5000 x 5000

Type

1-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

235 x 320

Guide Rail in mm

200 x 80

Classification

E 120

Size** [y x r] in mm

9400 x 18800

Type

2-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

400 x 610

Guide Rail in mm

300 x 150

Classification

EW 60

Size** [y x r] in mm

9400 x 18800

Type

2-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

400 x 610

Guide Rail in mm

300 x 150

Classification

EW 90

Size** [y x r] in mm

6800 x 4270

Type

2-tlg

Fabric

Heliotex 120

Wall Thickness* in mm

300

Housing (t x h) in mm

400 x 610

Guide Rail in mm

300 x 150

Alternatives for installation

Installation of the casing to the wall, thermomechanically

Housing

Open state

Closed state

Side Guides

FS-HC directly under the ceiling

Make an Inquiry

Protect your building with intelligent fire and smoke protection solutions engineered for performance, reliability, and architectural flexibility. Whether you’re planning a new project, upgrading an existing facility, or exploring specialized safety systems, Stöbich delivers advanced protection tailored to your exact requirements. Make an inquiry today and discover how our innovative fire protection technologies can help safeguard people, property, and operations with confidence.

Name(Required)
Email(Required)

About Our Fire Curtain HC

Fire Curtain HC is Stöbich’s advanced horizontal textile fire protection system designed to provide room enclosure, fire compartmentation, and radiation heat reduction in architecturally complex environments. Engineered for horizontal installation and motor-driven deployment, the system offers an innovative solution for protecting large open spaces where traditional vertical fire barriers may not be sufficient.

Why Horizontal Fire Protection Is Needed

Modern buildings increasingly feature:

  • Open floor plans
  • Large atriums
  • Skylights
  • Interconnected spaces
  • Complex ceiling designs
  • Multi-level architectural features

These design elements can create unique fire protection challenges that are not always addressed effectively by conventional vertical barriers alone.

Fire Curtain HC was developed specifically to provide horizontal fire separation where traditional compartmentation methods may be limited.

Advanced Horizontal Fire Compartmentation

Unlike traditional fire curtains that deploy vertically, Fire Curtain HC is designed for horizontal installation.

When activated, the system creates a room-enclosing textile barrier that helps:

  • Limit flame spread
  • Support compartmentation strategies
  • Protect designated building zones
  • Restrict the movement of hazardous conditions
  • Enhance overall fire safety performance

This unique deployment method expands the range of fire protection solutions available for complex architectural environments.

Radiation Heat Reduction

One of the system’s most important capabilities is its ability to help reduce radiant heat transfer during a fire event.

Controlling radiation heat is critical because excessive thermal energy can:

  • Accelerate fire spread
  • Increase occupant risk
  • Damage nearby structures
  • Impact evacuation safety
  • Compromise adjacent spaces

By reducing radiant heat transmission, Fire Curtain HC provides an additional layer of protection beyond basic fire separation.

Automatic Motor-Driven Deployment

Fire Curtain HC utilizes a reliable electric motor-driven closing mechanism.

When connected fire detection or alarm systems are activated, the curtain automatically deploys into position to create a protective horizontal barrier.

Benefits include:

  • Automatic activation
  • Rapid response during emergencies
  • Consistent deployment performance
  • Dependable operation when needed most
Concealed Architectural Integration

Fire Curtain HC is designed to remain visually unobtrusive during normal building operation.

Its housings and support structures can be concealed within:

  • Ceiling cavities
  • Architectural features
  • Building soffits
  • Surrounding structural elements

This allows designers to maintain open, contemporary spaces without introducing visually intrusive fire-rated assemblies.

Ideal for Architecturally Demanding Projects

The system is particularly well suited for projects where aesthetics and open design concepts are major priorities.

Common applications include:

  • Airports
  • Transportation terminals
  • Shopping centers
  • Museums
  • Performance venues
  • Hotels
  • Premium commercial developments

Fire Curtain HC allows architects to preserve expansive open spaces while maintaining effective passive fire protection strategies.

Greater Design Flexibility

Because Fire Curtain HC operates horizontally, it can protect areas and openings that may be difficult to address using standard vertical systems alone.

This provides architects and engineers with:

  • Greater design freedom
  • Flexible compartmentation options
  • Support for unconventional layouts
  • Solutions for specialized ceiling configurations
  • Enhanced fire protection planning capabilities

The result is a more adaptable approach to fire safety in complex building environments.

Engineered for Safety and Performance

Fire Curtain HC combines:

  • Horizontal fire curtain technology
  • Radiation heat reduction
  • Automatic motorized deployment
  • Room enclosure capabilities
  • Concealed architectural integration
  • Reliable fire compartmentation

Together, these features create an advanced fire protection solution that helps modern buildings remain visually open while maintaining critical life safety performance during emergency conditions.